本系列電流互感器適用于戶內, 額定頻率50Hz或60Hz, 額定電壓35kV及以下的小接地電流系統中供三相電纜接地保護用, 也可與繼電器配套使用。
安(an)裝時可將互感器分為(wei)兩半, 然后合并為(wei)一體, 用抱箍抱緊(jin)卡住, 可以在不停電(dian)狀(zhuang)態(tai)下進行安(an)裝。
This series of current transformers is used in indoor small ground current systems with rated frequency 50Hz or 60Hz and rated voltage up to and including 35kV for three-phase cable grounding protection, it also can be used with relay.
The transformer can be divided into two parts during installation, and then they can be combined again and buckled tightly with clamp. It can be installed without power off.
1、海拔:不超過1000米;
2、環境溫度:-5℃~+40℃;
3、空氣相對濕度:≤85%;
4、安裝場所:戶內。
1.Altitude should not exceed 1000m;
2.Ambient temperature: -5℃~+40℃;
3.Air relative humidity:≤85%;
4. Installation site: indoor。
1、額定二次電流:5A或1A;
2、功率因數:cosφ=0.8(滯后);
3、額定頻率:50Hz或者60Hz;
4、額定一(yi)次電流(liu)、 額定輸出及準(zhun)確級見表1;
5、耐壓試驗性能方面; 連續電機定子對二級電機定子及地和二級電機定子對地能承擔工頻耐壓試驗3kV經歷了1min。
1. Rated secondary current: 5A or 1A;
2. Power factor: cos中=0.8 (lag) ;
3. Rated frequency: 50Hz or 60Hz;
4.Rated primary current, rated output and accurate level see table 1.,
5.Insulating property: primary winding to secondary winding and ground, and secondary winding to ground can bear the power frequency withstand voltage 3kV for 1min.